- Home
- City Services
- Departments
- Building
- Public Right Of Way Design Details & Standards
- Water Distribution Specifications
Water Distribution Specifications
City of Wheaton Distribution Specifications - As of January 31, 2018
All Materials shall be as specified below or approved equal, be produced in North America, and be the current year model. All brass shall be “No-lead”, meeting the requirements of the Reduction of Lead in Drinking Water Act.
Water main
- Unless approved in writing all water main shall be 8” minimum size Class 52 Zinc-coated Ductile Iron pipe.
- If PVC water main is allowed, it must be approved in writing and shall be Certa-Lok PVC or equal. The design shall include two #10 Solid Insulated Copper tracer wires that terminate in a Copperhead Tracer Wire Access Box at each end. Shop drawings of the tracer wires must be submitted and approved for all PVC water main.
Polyethylene Wrap - Required on all Water Main Installations
- All ductile iron water main and fittings shall be encased with linear low-density V-Bio Enhanced polyethylene wrap, 8 mils thick. Polyethylene wrap shall be secured with polyethylene tape at overlaps, ends, and every four feet along the pipe barrel.
Fire Hydrants
- Mueller Super Centurian A-421, 4½ inch valve opening with 6-inch flange x mechanical A-2362 resilient wedge valve attached. All bolts shall be stainless steel on all valves and hydrants.
Gate Valves
- Mueller A-2362 (4-inch through 12-inch) or A-2361 (16-inch) resilient wedge gate valve
OR - American Series 2500 resilient wedge valve
Mechanical Joints
- EBAA Iron Mega-lug mechanical joint restraint gland
Tapping Valves
- Mueller A-2362 flange x mechanical joint resilient wedge valve
OR - American Series 2500 flange x mechanical joint resilient wedge valve
Tapping Sleeves - All Pressure Connections 4” to 8” Shall Be Done By The City Of Wheaton
- Smith-Blair 665 stainless steel tapping sleeve with stainless steel flange
OR - Ford FTSS stainless tapping sleeve with stainless steel flange
Valve Boxes
- Tyler Union 664S screw-type cast iron two-piece valve box
Note: Plastic valve boxes or plastic extensions are not allowed - Valve Box Adaptor II
- Type A Gate Valves - 4”-6” Mueller, 4”-6”-8” AFC
- Type B Gate Valves - 8” Mueller, 10”-12” AFC
- Type D Gate Valves - 10” Mueller
- Type E Gate Valves - 12” Mueller, 16” AFC
- Valve box extensions shall be Tyler Union #58, #60 or Tyler Union #69 riser.
End Caps
- Class “A” pipe: Tyler Union Mechanical Joint Cap.
- Class “B-C-D” pipe: Tyler Union MJ x PE Dual-Purpose Cutting-in Sleeve with Tyler Union Mechanical Joint Cap.
Service Fittings
- Corporation Cock
- Mueller 300 Ball Corporation Valve B-25000N
OR - Ford Corporation Stops FB600-size-NL
- Mueller 300 Ball Corporation Valve B-25000N
- Corporation Cock Quarter and Eighth Bends - ¾", 1", 1 ¼”, 1 ½” and 2"
- Mueller brass with compression ends and swivel nut. Flare nut, non-swivel accepted on sizes where others aren’t made. Mueller P-15075N, P-15076N
OR - Ford brass with compression ends and swivel nut. Flare nut, non-swivel accepted on sizes where others aren’t made. Ford LA04-size-NL, L04-size-NL.
- Mueller brass with compression ends and swivel nut. Flare nut, non-swivel accepted on sizes where others aren’t made. Mueller P-15075N, P-15076N
- Curb Stop
- Mueller 300 Ball Curb Valve P-25155N
OR - Ford Ball Valve Curb Stop B44-sizeM-NL
- Mueller 300 Ball Curb Valve P-25155N
- Curb Box
- Mueller H-10300 curb box with Minneapolis Pattern Base.
- Service Saddles
- Smith-Blair Model 317 Epoxy Coated Ductile Iron with double stainless-steel strap.